Maintenance Detective: The CIP That Wouldn’t Finish

Nov 5
3 min read

Updated: 16 hours ago

A 30-minute clean is taking hours, and the plant is paying for it.


The CIP recipe is simple. Run chemical at the target concentration through the machine for 15 continuous minutes, then rinse for 15 minutes. If soap concentration drops out of spec, the timer resets.


Every 5 or 6 minutes during the chemical cycle though, the conductivity reading drops to zero for a few seconds and then comes right back.


The timer resets each time, and the clean cycle starts over.


It is eventually completing the CIP, but it's taking hours.  


What we know:

  • The CIP skid sits in a dedicated cleaning room.

  • All sensors have been checked. All wiring has been checked. Both are good.

  • Pumps and a valve manifold sit next to the skid in the cleaning room.

  • The supply line runs up through the ceiling, travels across the overhead, and drops down to the machine.

  • The dropouts happen on a fairly regular rhythm.


Sanitation is losing hours every shift. Production is waiting on the line. Everyone wants to blame the sensor, but the sensor is fine.


What’s zeroing out the concentration reading?








Answer:


The answer: air.


Air was collecting in the high run of pipe in the ceiling. The sensor was reading exactly what was in front of it.


Here’s the mechanism.


A pump creates pressure at its outlet and vacuum at its inlet. If the suction side drops below atmospheric pressure, any leak upstream of the pump stops leaking out and starts pulling air in. A loose clamp, a worn gasket, or a weeping valve seat in the manifold can all do this.


That air travels with the solution up into the ceiling. The horizontal overhead run is the high point of the system, so the air collects there and the bubble grows. Eventually it gets big enough to choke the flow, and the system pushes it out all at once.


When that slug of air hits the conductivity sensor, there’s no liquid to conduct. The reading goes to zero for a few seconds, and the timer resets. The bubble rebuilds, and the cycle repeats every 5 or 6 minutes.


The giveaway: look at the manifold leaks. If a leak drips when the pump is off and stops dripping when the pump runs, the pressure inside that manifold is dropping below atmosphere. That means that the leak has become an air inlet.


You have three ways to fix it.

  1. Get rid of the vacuum at the inlet. Slow the pump creating the vacuum, remove a restriction on the suction side such as an undersized line, a throttled valve, or a clogged strainer, or otherwise raise the pressure in the area that’s pulling air.

  2. Seal the holes that let the air in.

  3. Put an Air Release Valve at the high point of the system to release collected air


If you cannot fix the manifold piping or add an air relief valve today, slowing the pump with a VFD or removing a restriction may be immediate solutions.


However, you're going to want to fix those leaks and an air relief valve in the high pipe section could make sense.


Don’t respond by adding a delay to the concentration alarm so the timer ignores short dropouts even if the quality guy will let you do it. That only hides the symptom, and it means chemical contact time on that clean is compromised.


And you're not going to want to explain that in an audit.