A PowerFlex 753 runs a hoist motor that raises and lowers loads all shift. Yesterday it started faulting, but only when lowering with a load.


Unloaded, it works fine.  It lifts a load fine.


The fault (F5, not one the tech has seen before) resets every time, and the next empty lift runs fine. Nobody has touched the parameters. The motor meggers good, the motor leads check out, and the incoming line voltage is steady.


The drive is clearly capable of moving this load and it's worked fine for years. 

 

So why can it raise the weight but not lower it?


What should I check?  Is the drive bad?











Answer:


The most likely answer is a cracked braking resistor.


Here’s why that only shows up on a loaded descent.


When the hoist raises a load, the motor is doing the work. Power flows from the line, through the drive, into the motor. That’s normal motoring.


When it lowers a heavy load, gravity is doing the work. The load drives the motor faster than the drive is commanding, so the motor becomes a generator.


That "regenerated" energy flows backward into the drive’s DC bus.


The drive’s input rectifier can’t push that energy back to the line, so it has two choices: store it in the bus capacitors (the voltage rises), or burn it off. Burning it off is the braking resistor’s job. When bus voltage crosses a threshold, a brake transistor switches the resistor across the bus and dumps the excess as heat.


With the resistor cracked open, the transistor still fires, but into nothing. Bus voltage climbs until the drive protects itself and trips on F5, High Voltage. The mechanical brake sets and the load stops.


That explains the pattern:

  • Raising, loaded or empty: motoring, so no regen and no problem.  Everything works fine.

  • Lowering empty: a little regen, which the drive’s own losses absorb. Everything works fine.

  • Lowering loaded: sustained regen for the whole descent, with nowhere to put it.  Drive Faults.


One thing that trips people up: on a conveyor or fan, regen mostly happens during decel.

On a hoist, it happens the entire time you’re lowering. That’s why lengthening the decel time doesn’t fix it.


How to prove it:

  1. Lock out the drive, wait out the discharge time on the label, and verify zero volts across DC+ and DC−. The resistor sits on the DC bus, and a working one can be hot enough to burn.

  2. Disconnect the resistor and ohm it. Compare the reading to the nameplate. You typically expect it to read within 10% of nameplate resistance.  An open reading is typical of a cracked resistor.

  3. Inspect the element. A cracked ceramic core or a broken wire element can look nearly normal from a distance.


The fix:

Replace the resistor with one rated for the correct ohms and wattage. Then ask why it cracked: undersized watts for the duty cycle, heat cycling, vibration from the mounting location, or poor airflow around it.


Like all electrical components, brake resistors need to be kept clean, tightly connected, and cool.