Maintenance Detective: The Tripped Motor Overload
The call: a conveyor is down. The overload on the motor starter has tripped. The setup: • 240V, 3-phase supply • Dual-voltage motor, wired for low voltage • Across-the-line starter with an overload relay Before I do anything, I verify I have followed all of my organization's safety protocols. And since I'm already in the panel, I put my meter on the load side (bottom) of the tripped overload and check the motor circuit phase-to-phase: Blue – Red: OL Red – Black: 1.2 Ω Black –