Maintenance Detective: The Tripped Motor Overload
The call: a conveyor is down. The overload on the motor starter has tripped. The setup: • 240V, 3-phase supply • Dual-voltage motor, wired for low voltage • Across-the-line starter with an overload relay Before I do anything, I verify I have followed all of my organization's safety protocols. And since I'm already in the panel, I put my meter on the load side (bottom) of the tripped overload and check the motor circuit phase-to-phase: Blue – Red: OL Red – Black: 1.2 Ω Black –

Mac Davis
4 min read


Electrical Preventive Maintenance: Tight, Cool, Dry, and Clean
Most electrical failures give you plenty of warning. But plants just aren’t looking. And they're usually easier to prevent than to troubleshoot or repair. A good electrical PM comes down to four words: tight, cool, dry, and clean. Tight. A loose connection adds resistance. Resistance under load makes heat, and the heat oxidizes the connection. Resistance climbs, makes more heat, and it feeds itself until something burns. I recommend checking every lug in each cabinet annually

Mac Davis
3 min read


Maintenance Detective: Gremlins in the Drives
First time it happened, no big deal. We just power cycled the machine and it went away. One drive in a bank of them dropped out mid-shift: the fault said something about "F111 Safety Hardware". Machine just shut down and wouldn't run. No E-stop pressed. No gate opened. Safety relay had all green lights, no issue there. After power cycling, the machine fired up and ran the rest of the shift with zero complaints. Then nothing for three weeks. Then it came back. Once a week

Mac Davis
4 min read